Flame detector

PUO-35Ex



Type:
Conventional, flame detector (UV) - intrinsically safe

Principles of operation:
The PUO-35EX flame detector is designed for detection and signalisation of a flame ignition in case of a fire hazard. In the moment of fire hazard the detector transmits an alarm signal to the fire alarm control panel.

Cooperation:

The PUO-35EX detectors can operate in  lines/loops of the IGNIS 1000/2000 or on the side line of ADC-4001M adapter in POLON 4000 fire alarm control panels.

Type

conventional

Category

to work in normal conditions

Type

flame

Operational voltage

17 VDC - 24 VDC

Quiescent current consumption

< 100 µA

Current consumption in alarm mode

20 mA

Detector class

text

Addressing

conventional detector without addresses

Operating temperature range

from -10°C to 55°C

Relative humidity

to 93% at 40°C

Dimensions of detector with base

Ф107 x 60mm

Weight

0.45 kg

Enclosure colour

black

Other parameters

Viewing range - max 17 m (2 sensitivity class), Supervision angle 120⁰, Detected radiation band - UV